Note: You will need to have 1 of the following options available or this can not be completed in the field. - Do you have a PC with A200 software installed?
- If so, you can physically install the card into that machine and run a batch file to 'flash' the firmware to Automation1
- Do you have an A3200 installer?
- If so, you can remove Automation1 software, install A3200, run the batch file, & re-install Automation1
- If you have none of the above, the card will have to be returned to Aerotech to flash the firmware for you
The following instructions assume that you are starting with a motion system based on: - A PC with the A3200 software-based machine controller installed.
- The PC has a HyperWire card installed with A3200 firmware on the HyperWire card.
- The drives on your system are Automation1 drives with A3200 drive firmware installed, enabling those Automation1 drives to communicate to the A3200 controller over HyperWire.
- If these drives have Automation firmware above 2.00, you can skip step 4
Please Complete the Following steps:- Connect and power the drives that you wish to convert from A3200 to Automation1. Using the A3200 firmware loader, make sure that the HyperWire card and Automation1 drives have the same firmware on them.
- Download the A3200toAutomation1.zip file and save the “A3200-to-Automation1-2.4.1.loda” and “Load Automation1 Firmware.bat” files to your PC.
- Open A3200 Firmware Loader and ensure that all of the drives that you want to convert are listed.
- Use A3200 Firmware Loader to load A3200-to-Automation1-2.4.1.loda onto the drives. Verify that no error messages are printed in A3200 Firmware Loader.
- Completely uninstall the A3200 from your computer.
- Install the Automation1 MDK and Automation1 iSMC versions 2.0.0 or later.
- Download Load Automation1 Firmware.bat to your Desktop.
- Double-click Load Automation1 Firmware.bat. Follow the instructions in the window that pops up. Here is the output that you should see when you run Load Automation1 Firmware.bat: